| Lithium Fire Test |
|
|
|
OVERALL EVALUATION AND CONCLUSIONSBased on the results of these tests, it was shown that Arctic Fire-Freeze™ (AFF) is unsurpassed in extinguishing lithium fires in record times. The FAA Report (cited above) shows that Halogen type agents are "ineffective" for extinguishing "primary" Lithium Battery fires, while AFF can extinguish the fire and provide instant cooling. This type of extinguishment would be applicable in "primary" Lithium Battery Fires (including fires from computer batteries, camera batteries, etc.). In completely extinguishing AND cooling the three (3) "Primary" Lithium Batteries which were ignited, only 2 quarts of AFF was necessary for both extinguishment and cooling. Further, the total time required for extinguishment was as low as ten (10) seconds. DATE: April 15, 2007 LOCATION: Rural Tulsa - OklahomaParticipants/Observers:
Test Conditions:
Photo 01
ANALYTICAL DATA
Test Plan:
Historical:
GSL Test 04415:
Photo 02
Extinguisher Data:
Extinguishment:
Photo 03
Time Required For Extinguishment:
Quantity Applied:
Final Observation:
|